Under both the IPC and the UPC, the liquid seal of a standard fixture trap must fall within what range?
1 in. to 2 in.
2 in. to 4 in.
4 in. to 6 in.
6 in. to 8 in.
Show the answer
B. 2 in. to 4 in.
Both model codes call for a seal of at least 2 in. and no more than 4 in. Less than 2 in. is too easily lost to pressure changes and evaporation; a much deeper seal slows flow and collects solids.
Under the Safe Drinking Water Act, solder and flux used on potable water piping may contain no more than what percentage of lead?
0.25 percent
0.2 percent
8 percent
50 percent
Show the answer
B. 0.2 percent
The Act defines lead free for solder and flux as not more than 0.2 percent lead. 0.25 percent is the separate limit for wetted surfaces of pipe, fittings and fixtures, and 8 percent was the old limit for pipe and fittings before 2014.
Reference: Safe Drinking Water Act, Section 1417 (42 U.S.C. 300g-6)
Why is a propane leak in a basement or pit especially dangerous?
Propane is lighter than air and collects at the ceiling
Propane is heavier than air and collects in low areas
Propane has no odorant and cannot be smelled
Propane burns only when it is mixed with natural gas
Show the answer
B. Propane is heavier than air and collects in low areas
Propane vapor has a specific gravity of about 1.5, so it flows downward and pools in basements, pits and trenches where it can reach an ignition source. Like natural gas, commercial propane is odorized so leaks can be noticed.
Reference: NFPA 58 (LP-gas properties); NFPA 54
A column of water about how tall produces a pressure of 1 psi at its base?
0.433 ft
27.7 ft
34 ft
2.31 ft
Show the answer
D. 2.31 ft
Each foot of water gives 0.433 psi, so 1 psi takes 1 / 0.433 = 2.31 ft. 0.433 is the psi per foot, not feet per psi. 27.7 is the number of inches (not feet) of water column in 1 psi, and 34 ft is roughly the head equal to atmospheric pressure.
Reference: Hydrostatics: 0.433 psi per foot of head
A clothes washer's solenoid valves cause loud banging in the supply piping. Which correction is the recognized one?
Install water hammer arresters near the valves
Install a larger water meter and service line
Install a backflow preventer at the washer box
Install a vacuum relief valve on each supply
Show the answer
A. Install water hammer arresters near the valves
A water hammer arrester has a sealed air or gas cushion that absorbs the pressure wave, and it works best close to the quick-closing valve. Backflow preventers and vacuum relief valves deal with reverse flow and negative pressure, not shock.