What does the fixed maximum liquid level gauge (bleeder valve) tell the person filling a propane tank?

  1. The pressure inside the tank in psi
  2. The temperature of the liquid in the tank
  3. That the tank has no air or water in it
  4. That the liquid has reached the maximum fill level
Show the answer

D. That the liquid has reached the maximum fill level

A dip tube ends at the maximum permitted liquid level. During filling the bleeder is opened; when it changes from clear vapor to a white liquid mist, the tank is full and filling stops.

Reference: NFPA 58 Sections 5.9 and 7.4 (fixed maximum liquid level gauge)

Under the DOT rules now in force, a new propane cylinder must first be requalified within how many years of its manufacture date?

  1. 5 years
  2. 7 years
  3. 12 years
  4. 20 years
Show the answer

C. 12 years

A DOT specification propane cylinder must be requalified within 12 years of the manufacture date stamped on its collar. The 5-year period applies after a requalification done by external visual inspection.

Reference: 49 CFR 180.209; NFPA 58 Section 5.2

A customer brings in a cylinder whose requalification date has passed. What must the filler do?

  1. Fill it to half of its capacity only
  2. Refuse to fill it until it is requalified
  3. Fill it and tag it for later inspection
  4. Fill it if the valve has a triangular wheel
Show the answer

B. Refuse to fill it until it is requalified

A cylinder that is out of date may not be filled until it has been requalified. A good valve does not make up for an expired cylinder, and partial filling is not an exception.

Reference: 49 CFR 180.205; NFPA 58 Chapter 7 (filling of cylinders)