What is the general minimum size of an air gap, measured vertically above the flood level rim?

  1. Equal to the diameter of the supply outlet's effective opening, and never less than 1 inch
  2. Twice the diameter of the drain outlet of the receptor, and never less than 2 inches
  3. Twice the diameter of the supply outlet's effective opening, and never less than 1 inch
  4. Three times the diameter of the supply pipe upstream, and never less than 6 inches
Show the answer

C. Twice the diameter of the supply outlet's effective opening, and never less than 1 inch

The basic rule is two times the effective opening of the supply outlet with a 1 inch minimum. A gap equal to one diameter is too small to stop water from bridging during a vacuum.

Reference: ASME A112.1.2 air gap principles; EPA Cross-Connection Control Manual (EPA 816-R-03-002), ch. 4

A faucet with a 3/4-inch effective opening discharges into an open tank away from any wall. What minimum air gap is needed above the tank's flood level rim?

  1. 3/4 inch
  2. 1-1/2 inches
  3. 1 inch
  4. 2-1/4 inches
Show the answer

B. 1-1/2 inches

Two times the 3/4-inch effective opening is 1-1/2 inches. One inch is only the floor that applies when twice the opening would come out smaller than that.

Reference: ASME A112.1.2 air gap principles; EPA Cross-Connection Control Manual (EPA 816-R-03-002), ch. 4

A supply outlet with a 3/8-inch effective opening fills an open sump away from any wall. What minimum air gap applies?

  1. 3/4 inch
  2. 3/8 inch
  3. 1-1/8 inches
  4. 1 inch
Show the answer

D. 1 inch

Twice 3/8 inch is 3/4 inch, but an air gap is never less than 1 inch, so 1 inch governs. Stopping at 3/4 inch forgets the minimum.

Reference: ASME A112.1.2 air gap principles; EPA Cross-Connection Control Manual (EPA 816-R-03-002), ch. 4