Hydraulics practice questions

26 questions from the backflow prevention tester practice test.

Hydraulics practice test

10 questions, graded as you go, with the reason for every answer. No sign-up.

What this covers

Sample questions

One psi of pressure will support a column of water about how high?

  1. 0.433 ft
  2. 14.7 ft
  3. 33.9 ft
  4. 2.31 ft
Show the answer

D. 2.31 ft

One psi equals about 2.31 feet of water (1 divided by 0.433). The value 0.433 is psi per foot, the conversion going the other way.

Reference: Hydraulics constants: 2.31 ft of head per psi

A gauge on a water line at sea level reads 50 psig. What is the absolute pressure in the line?

  1. 64.7 psia
  2. 35.3 psia
  3. 50.0 psia
  4. 14.7 psia
Show the answer

A. 64.7 psia

Absolute pressure is gauge pressure plus atmospheric pressure: 50 + 14.7 = 64.7 psia. Subtracting 14.7 instead gives 35.3, which is the common slip.

Reference: Hydraulics: psia = psig + atmospheric pressure

Which event is most likely to cause backsiphonage in a building's water service?

  1. A booster pump starting up on the building's domestic water piping system
  2. A water heater firing while no fixtures are being used
  3. A break in the water main at a lower elevation down the street
  4. A pressure-reducing valve failing in the wide-open position
Show the answer

C. A break in the water main at a lower elevation down the street

A main break at a lower elevation drains the main and can pull pressure at higher services below atmospheric, siphoning water backward. A booster pump raises downstream pressure, which is a backpressure cause rather than a backsiphonage cause.

Reference: Backflow hydraulics fundamentals; EPA Cross-Connection Control Manual (EPA 816-R-03-002), ch. 2